摘要
介绍了供给非正弦负载变压器谐波损耗的简易数字测量方法: 仅用与变压器输出端电压、电流工频分量相对应的有功功率P21和传输给负载的有功功率P2 间的差值来表示变压器中的谐波损耗, 不必使用高压侧的传感器, 且P21和P2都是从处理相同数字信号的同一仪表中获取, 因此该测量方法不仅简单易行, 而且测量结果更加准确。
This paper describes a simple digital measurement of harmonic losses in transformers supplying the distorting load.The method only uses the difference between the fundamental active-power P_(21) measured in output terminal and P_(2) delivered to the load, also measured in output terminal,to express harmonic losses in transformers,and so high-voltage transducers are not necessary.Moreover,both P_(21) and P_(2) can be obtained from the same instrument processing the same digital signal.Therefore,the method is not only easy and simple in implementing,but also more accurate in its measurement results.
出处
《广东电力》
2005年第4期20-22,共3页
Guangdong Electric Power
关键词
数字测量
电流畸变
谐波损耗
准确性
digital measurement
current distortion
harmonic loss
accuracy