国产大型发电机变压器组及辅助变压器微机保护的调试和运行(二)

Operation and Commissioning of Microcomputer Protection for Large Generator - Transformer Bank and Auxiliary Transformer Made in China
下载PDF
导出
摘要 (上接2005年第5期P34) 3.2.3主变压器低压侧接地保护动作问题 该保护是在发电机出口开关断开时,作为主变压器低压侧、厂用变压器高压侧及相应的离相封闭母线的接地保护. According to the summary of Operation and commissioning of microcomputer protection for large generator - transformer bank and auxiliary transformer in phase 2 of Qinshan, the existent problems of the microcomputer protection were analyzed, including self- holding of outlet of generator -transformer bank, diflerential protection of main transformer, differential protection of 500 kV side, suppression device of secondary harmonics. Analysis on the causes of miss operation and its corresponding countermeasures are put forward, and the suggestions to improve the method of frequency measurement, record wave file and alarm lamp are presented.
作者 李德佳
出处 《电力设备》 2005年第6期34-36,共3页 Electrical Equipment
关键词 发电机变压器组 微机保护 运行 调试 国产 离相封闭母线 厂用变压器 出口开关 主变压器 接地保护 低压侧 高压侧 断开 microcomputer protection generator transformer operation and commissioning