期刊文献+

复式比率制动差动元件中制动系数取值分析 被引量:1

Selecting Magnitude of Ratio Check Coefficient in Complex Percentage Differential Relay
下载PDF
导出
摘要 在制动量中引入差动电流,构成复式比率制动特性.该特性制动系数的选取,应保证在内部短路故障时,计及流出母线电流的情况下,差动元件也能可靠动作;在外部短路故障,TA饱和而产生较大的误差时,也能保证安全性.通过分析提出同时兼顾内外故障时制动系数的取值范围;同时说明了双母线分裂运行和并列运行时差动保护的大差元件应取高低不同的制动系数. With the differential current introduced in restraint portion, the complex percentage check characteristic is made up. The selection of magnitude of ratio check coefficient must ensure that the differential relay can operate firmly even when a fault occurs in a bus internally and the outflow of bus current exists, and that the differential relay do not operate even when the TA saturation brings about errors which are out of protection zone. This paper proposes a selection area of ratio check coefficient, which fits both the internal and the external faults, and points out that the check coefficient of large differential relay must be differentiated, when bus is operating in break-up or in parallel.
作者 罗士萍
出处 《南京工程学院学报(自然科学版)》 2005年第1期18-22,共5页 Journal of Nanjing Institute of Technology(Natural Science Edition)
关键词 母差保护 复式比率制动 制动系数 bus-bar differential protection complex percentage check check coefficient
  • 相关文献

参考文献2

二级参考文献2

  • 1朱声石.高压电网继电保护原理与技术[M].北京:中国电力出版社,1995..
  • 2王春生.母线保护[M].中国电力出版社,1997,10..

共引文献11

同被引文献7

  • 1阴宏民,宋小舟,马晓红.BUS-1000型母线保护存在的问题及解决方案[J].电力设备,2006,7(10):61-64. 被引量:1
  • 2王春生,等.母线保护[M].北京:中国电力出版社,1997.
  • 3深圳南瑞科技有限公司.BP.2B微机母线保护装置技术说明书[Z].深圳:深圳南瑞科技有限公司,2006.
  • 4南瑞继保电气有限公司.RCS.915微机母线保护装置技术说明书[Z].南京:南瑞继保电气有限公司,2004.
  • 5许继电气股份有限公司.WMH-800A微机母线保护装置技术说明书[Z].许昌:许继电气股份有限公司,2007.
  • 6北京四方继保自动化股份有限公司.CSC-150数字式母线保护说明书[Z].北京:北京四方继保自动化股份有限公司,2005.
  • 7孙建华,黄文载,匡华.微机母线差动保护比率制动系数应用研究[J].云南电力技术,2008,36(2):19-21. 被引量:3

引证文献1

二级引证文献3

相关作者