期刊文献+

低压线路无功补偿装置谐波保护的实验研究 被引量:6

Experimental research on harmonic protection of reactive power compensation device for low voltage line
下载PDF
导出
摘要 现有低压线路无功补偿装置不具备谐波监测与保护功能,由于谐波干扰造成装置退出运行、电容器损坏的事故频繁发生,严重影响装置安全运行和电网经济运行水平。应用数字信号处理器TMS320C32设计实现了低压线路无功补偿装置的谐波实时监测与保护,实验研究与现场运行表明,该方法能够有效地提高现有装置抵御谐波干扰的能力和并联补偿电容器运行的可靠性。 With the objective of overcoming the shortcomings of low voltage line reactive power compensation device, based on harmonic data from the running field, actual harmonic level, system voltage, system circuits and running situation of the compensation device, the harmonic protection module is designed with digital FFT method in software program. The digital signal processor is used. The real time monitoring and protecting of Harmonic wave for low voltage line reactive power compensation device is realized. Experimental results and field running situations indicate mat this device is effective.
作者 王飞 米增强
出处 《华北电力大学学报(自然科学版)》 CAS 北大核心 2005年第4期16-19,共4页 Journal of North China Electric Power University:Natural Science Edition
关键词 谐波 无功补偿 数字信号处理器 harmonic reactive power compensation DSP
  • 相关文献

参考文献6

二级参考文献20

  • 1吴竟昌.供电系统谐波[M].北京:中国电力出版社,1998..
  • 2林海雪.国际电工委员会谐波标准简介[J].中国电力,1998,10.
  • 3王晓毛 张淼 等.并联有源电力滤波器直流侧电压模糊控制.中国首届电子电源及功率自关断器件应用技术研讨会[M].合肥,-.258-261.
  • 4王幸之.单片机应用系统抗干扰设计[M].北京:北京航空航天大学出版社,2000..
  • 5吴竞昌,供电系统谐波,1998年
  • 6许实章,电机学,1988年
  • 7王幸之.单片机应用系统抗干扰设计[M].北京:北京航空航天大学出版社,2000..
  • 8林海雪.从IEC电磁兼容标准看电网谐波国家标准[J].电网技术,1999,23(5):64-67. 被引量:40
  • 9刘晓川,何迈,刘俊勇,李兴源.变电站电压/无功模糊控制的理论研究[J].四川联合大学学报(工程科学版),1999,3(4):124-129. 被引量:8
  • 10赵渊,钟岷秀,周念成,张林.电力系统谐波分析仪算法研究[J].华东电力,1999,27(4):15-17. 被引量:10