摘要
根据电网频率运行的要求,对表征电网频率特性的频率衰减时间常数Tf、静态负荷频率调节系数KL进行了试验研究和理论分析计算。对系统功率缺额频率滑差6f/dt和负荷频率反馈df/dt进行了识别,为SZH-2型数字周波继电器的df/dt整定和低电压闭锁整定提供了可靠的参考。
According to the importance of frequen-cy in power system operation,the authors tested andcalculated the frequency attenuation time constant Tfand the static load frequency coefficient KL,whichcharacterinze the frequency variation of power system.In this paper the frequency deviation df/dt caused bypower shortage and the load frequency feedback df/dtare discriminated,it provides a reliable basis for thesetting of digital frequency relay.
出处
《电网技术》
EI
CSCD
北大核心
1995年第12期43-47,53,共6页
Power System Technology
关键词
电网
频率特性
负荷反馈
Frequency deviation Power system Load feedback