摘要
变压器在空载合闸时将产生很大的励磁涌流,这种励磁涌流对变压器的稳定运行极为不利。为削减这种励磁涌流,提出了3种方法:控制三相开关合闸的时间法,内插电阻法和改变变压器绕组的分布法。理论分析和实验表明,这3种方法各有其优缺点,都能有效地削减励磁涌流,前两种方法的可行性更好。
Large inrush current occurs when energizing unloaded transformer in power system, which provides unfavorable condition in transformer operation. Three methods are proposed in this paper to reduce inrush current: by controlled three-phase switching; by resistor insertion and by changing the distribution of coil winding. The three methods are proved to be effective both by the theoretical and practical considerations which all have advantages and disadvantages, but the feasibility of the former two methods is better.
出处
《高压电器》
EI
CAS
CSCD
北大核心
2005年第4期282-285,共4页
High Voltage Apparatus
关键词
变压器
励磁涌流
控制开关
剩磁
内插电阻
分布比率
transformer
inrush current
controlled switch
residual flux
resistor insertion
distribution ratio