中性点不接地系统两点异地接地距离保护探析 被引量:1

Discussion on Two-point Grounding Distance Protection in Neutral Non-grounding System
下载PDF
导出
摘要 分析了中性点不接地系统发生异地两点接地故障时,相间距离和接地距离保护动作行为,结果表明两种距离保护均可能出现误动现象。为防止误动,提出了设置零序启动元件、零序闭锁元件及故障相电压与被保护线路故障相电压降比值的新判据,判据简单、可靠。 This paper analyzes the protective action of inter phase distance and grounding distance when two-point grounding fault in different spots occurs in neutral non-grounding system.The results show that maloperation may happen in both of distance protection.In order to prevent the maloperation,a new criterion is put forward by setting up zero sequence starting and blocking element and reducing voltage ratio between fault and protected lines phase voltage.This criterion is simple and reliable.
出处 《水电能源科学》 北大核心 2010年第9期158-160,共3页 Water Resources and Power
关键词 中性点不接地系统 接地距离保护 相电压 两点接地故障 故障相 启动元件 系统发生 误动现象 新判据 零序 动作行为 保护线路 距离和 电压降 结果 分析 闭锁 比值 neutral non-grounding system two-point grounding in different spots distance protection zero sequence element voltage ratio