摘要 基于110 kV连南线同塔双回垂直排列线段现状和舞动模型调查,分析了导线的舞动原因,研究了导线发生舞动机理,提出了无覆冰的邓哈托舞动模式。并比较分析了集中安装重锤和相间间隔棒两种方案。结果表明,选择相间间隔棒方案可治理导线舞动,提高了输电线路的供电可靠性和健康运行水平,为输电线路因特殊风向诱发的邓哈托舞动模式治理提供了参考依据。 Based on investigation of the status of 110 kV Liannan transmission line double circuit section where the line is vertically arranged on the same tower,and the swaying pattern,the main cause of the wire swaying is analyzed.Then,the swaying mechanism of the wire is studied,and the Den Hartog swaying pattern without ice coating is put forward.Specifically,two schemes,centralized heavy-punch installation and inter-phase spacers,are compared.The results show that the scheme of inter-phase spacers can bring the wire swaying under control and enhances the reliability and safety of the power supply transmission lines,which provides basis for regulation of the Den Hartog pattern swaying induced by particular wind directions in transmission lines.
机构地区 宁夏吴忠供电局
出处 《水电能源科学》 北大核心 2010年第8期148-150,120,共4页 Water Resources and Power
  • 相关文献

参考文献3

  • 1朱宽军,付东杰,王景朝,孙娜.架空输电线路的舞动及其防治[J].电力设备,2008,9(6):8-12. 被引量:32
  • 2DL/T 741-2001.架空送电线路运行规程[S],2001.
  • 3国家电力公司东北电力设计院编著,张殿生.电力工程高压送电线路设计手册[M]中国电力出版社,2003.

二级参考文献7

共引文献31

同被引文献5

  • 1董吉谔.电力金具手册(第二版)[M].北京:中国电力出版社.2007.
  • 2国家电力科学研究院,国家电网公司,华北电网有限公司,等.架空输电线路运行规程(DL/T741-2010)[S].北京:中国电力出版社,2010.
  • 3国家电网公司,中国电力工程顾问集团公司,华东电力设计院,等.110-750kV架空送电线路设计技术规定(Q/GDWl79-2008)[S].北京:中国电力出版社,2008.
  • 4中国电机学工程学会输变电专业委员会.超高压架空输电线路张力架线施工工艺导则(SDJJS2-87)(试行)[S].水利水电部基本建设司,1987.
  • 5国家电网公司公司工程建设部,国电电力建设研究所,中国电机工程学会输电线路专业委员会施工技术分会,等.110-500kV架空送电线路施工及验收规范(GB502332005)[S].北京:中国计划出版社,2005.