根尖孔直径对Root ZX和Neosono Ultima EZ测量准确性的影响 被引量:7

The influence of diameters of root canal foramen on the accuracy of Root ZX and Neosono Ultima EZ
原文传递
导出
摘要 目的:研究根尖孔直径对两种根管长度电测仪Root ZX和Neosono Ultima EZ测量准确性的影响。方法:采用琼脂凝胶模型和毛细玻璃管模拟体内根管,以15#不锈钢K锉为测量电极,在两种不同测量环境下(干燥或2.5%NaClO)使用Root ZX和Neosono Ultima EZ下测量毛细玻璃管的长度,记录测量值与实际值之间的差值(IF值)。结果采用相关分析。结果:Root ZX的IF值在干燥条件下与玻璃管直径无相关,而在有电解质的条件下(2.5%NaClO)随玻璃管直径增大而增大(P<0.05),Neosono Ultima EZ的IF值在不同测试条件下都与玻璃管直径无相关。结论:Root ZX的准确性在有电解质存在的条件下与根尖孔的直径呈负相关,而Neosono Ultima EZ的测量准确性在有无电解质条件下都不受根尖孔直径的影响。 Objective:To investigate the effect of diameter of root canal foramen on the accuracy of two apex locators. Method: Use the agar model and glass capillaries to mimic root canals in vivo. Record the distance between measured length and the real length of the capillaries as the IF value by using a No. 15 stainless steel K file, Root ZX and Neosono Ultima EZ under two measuring environments (dry and 2.5% NaClO). All the data were subject to correlation analysis. Result:The IF values of Root ZX had no relation to the diameters of capillaries when the capillaries were dry, but had positive proportion to the diameters of capillaries (r〉0, P〈0.05) with the capillaries full of 2.5 % NaClO solution. The IF values of Neosono Ultima EZ had no relation to the diameters of capillaries under both measuring enviroments. Conclusion: The accuracy of Root ZX is reverse to the diameter of root canal foramen with electrolytes in the root canal. The accuracy of Neosono Ultima EZ is not impacted by the diameter of root canal foramen under various measuring enviroments.
出处 《临床口腔医学杂志》 2005年第9期526-527,共2页 Journal of Clinical Stomatology
关键词 电测仪 根尖孔 直径 准确性 electronical apex locator apical foramen, diameter accuracy
  • 相关文献

参考文献10

  • 1Huang L. An Experimental study of the principle of electronic Root Canal measurement [ J ]. J Endodon, 1987,13(2) :60 - 64.
  • 2Jenkins JA, Walker WA, Schindler WG, et al. An in vitro evaluation of the accuracy of the Root ZX in the presence of various irrigants[J]. J Endodon 2001,27(3) :209 - 211.
  • 3Kobayashi C, Suda H. New electronic canal measuring device based on the ratio method[ J ]. J Endodon, 1994,20 (3): 111 - 114.
  • 4Aurelio JA, Nahmias Y, Gerstein H. A model for demonstrating an electronic canal-length measuring device[J]. J Endodon, 1983,9(1 ):568 - 569.
  • 5Shrader C, Sener B, Barbakow F. Evaluation the sizes of lightspeed instruments[J]. Inter Endo J, 1998,31(4) :295 - 300.
  • 6Ounsi HF, Naaman A. In vitro evaluation of the reliability of the root ZX electronic apex locator [ J ]. Inter Endo J, 1999, 32 (3): 120 -123.
  • 7Vajrabhaya L, Tepmongkol P. Accuracy of apex locator[J]. Endod Dent Traumatol, 1997,13(4): 180 - 182.
  • 8Meares WA, Steiman RH. The influence of sodium hypochlorite irrigation on the accuracy of the Root ZX electronic apex locator[J ]. J Endodon ,2002,28(8): 595 - 598.
  • 9Kobayashi C. Electronic canal length measurement[J ]. Oral Surg Oral Med Oral Path, 1995,79(2): 226 - 231.
  • 10Kaufman A V, Katz A. Reliability of Root ZX apex locator tested by an in vitro model[J]. J Endod, 1993,19(4) :201.

同被引文献26

  • 1沙鑫家,朱文忠,孙汉堂.ProPex根管测量仪测量磨牙牙齿操作长度准确性的临床评价[J].牙体牙髓牙周病学杂志,2005,15(11):621-623. 被引量:7
  • 2曹东,梁景平.Root ZX根管长度测量仪的临床应用评价[J].口腔材料器械杂志,2006,15(3):122-124. 被引量:4
  • 3覃荣林,朱霞.影响根管长度电测仪测量效果的因素分析[J].上海生物医学工程,1996,17(3):27-28. 被引量:14
  • 4Morfis A, Sylaras SN, Georqopoulou M, et al. Study of the apices of human permanent teeth with the use of a scanning electron microscope [J]. 1994, 77 (2): 172.
  • 5Kobayashi C. Electronic canal length measurement [J]. Oral Surg Oral Path Oral radiol Endod, 1995, 79 (2) : 226.
  • 6[1]Huang L.Experimetal study of the princin of electronic Root Canal measurement[J].J Endodon,1987,13(2):60-64
  • 7黄力子.根管长度电测法及原理[J].中华口腔医学杂志,1988,23(5):297-297.
  • 8岳松龄.口腔内科学[M].第2版,北京:人民卫生出版社,1986:224.
  • 9Morris A, Sylaras SN, Georgopoulou M ,et al . Study of the apices of human permanent teeth with the use of a scanning electron microscope[ J]. Oral Surg Oral Med O-ral Pathol , 1994(2) : 172 - 176.
  • 10Frank AL,Torabinejad M. An in vivo evaluation of Endex electronic apex locator[J]. J Endod,1993(4) : 177 - 179.

引证文献7

二级引证文献10

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部