期刊文献+

一种实用的馈线单相接地故障区段定位与隔离方法 被引量:20

Practical Method of Locating and Isolation for Single Phase Grounding Fault Section of Feeders in Distribution Networks
下载PDF
导出
摘要 为解决小电流接地系统单相接地故障定位困难的问题,介绍了一种在电压时间型馈线自动化系统中基于零序电压检测的馈线单相接地故障区段定位与隔离方法,阐述了该方法的工作原理和馈线终端单元(FTU)的运行方式。以中山市某区环网型线路馈线自动化系统工程为例,论述了基于该方法的单相接地故障区段定位与隔离的过程分析,验证了该方法的可行性和实用性。 In order to solve the problem of single phase grounding fault locating in non-effectively grounding networks, a zerosequence voltage based practical method of locating and isolating for single phase grounding fault section is proposed in this paper, which operates on the feeder automation system of Voltage-time type, The main principle about this method is given and the operating mode of feeder terminal unit (FTU) is also discussed. At last, combined with the project of a Zhongshan loopfeeder automation system, the analysis about fault insulating process is described in detail. It is demonstrated that the method proposed is feasible and practical.
出处 《电力系统自动化》 EI CSCD 北大核心 2005年第19期79-81,共3页 Automation of Electric Power Systems
关键词 小电流接地系统 单相接地 电压时间型 零序电压 FTU non-effectively grounding network single phase grounding voltage-time type zero-sequence voltage feeder terminal unit(FTU)