摘要 参考美国和我国台湾地区的技术文献以及我国国家标准,对某医学中心的冰蓄冷工程进行测试,从技术性指标和经济性指标等角度进行分析评估。结果表明,由于技术及管理方面的原因,蓄冰装置的蓄冷性能有所下降,但释冷特性较好,一般能释放所蓄的全部冷量,投资回收期为5.1年。通过对该工程的测试与分析得知优化设计和优化运行是发挥冰蓄冷系统优势的关键。最后,总结冰蓄冷系统优化设计和优化运行的一些方法。 The ice storage system of a medical center is tested and analyzed from the technical index and the economic index by consulting the technique information from American and Taiwan district and our national standards. The result indicates that the performance of the ice storage device is descending, but the discharge property is relatively satisfactory for almost all the charge capacity can be released and the recovery period is 5.1 years. The conclusion is drawn that the optimal design and optimal running of ice storage system is important by this test and analysis. At last, the solutions to optimal design and optimal running of ice storage system are illustrated.
出处 《上海海事大学学报》 北大核心 2005年第3期14-17,共4页 Journal of Shanghai Maritime University
关键词 蓄冰装置 蓄冷循环 释冷特性 蓄冷量 ice storage device charge cycle discharge characteristic charge capacity