摘要
结合西北330kV电网的实际,本文详细分析了取消330kV断路器合闸电阻后的系统合问、重合间过电压及MOA吸收能量,得出了大部分330kV线路可以取消断路器合闸电阻的结论。在线路两侧加装MOA的情况下,更多的线路可取消断路器的合闸电阻。
According to the practical situations of 330kVpower system in Northwest China and under the conditionof eliminating closing resistors for 330kV circuit breakers,the switching-surge overvoltages and the MOA energy dissipation is analyzed in this paper, and it is proved from theanalyses that the bulk of reclosing resistor for most 330kVcircuit breakers can be eliminated. Installing MOA at bothendes of the transmission line, it is possible for more transmission line to eliminate the closing resistor for 330kV circuit breakers.
出处
《电网技术》
EI
CSCD
北大核心
1996年第2期8-11,共4页
Power System Technology
关键词
断路器
合闸电阻
避雷器
电网
Closing resistor for circuit breaker MOAenergy dissipation Switching - surge overvoltage Absorbed energy