摘要
蒸发式冷凝器的夏季工况是一个既有热量传递又有质量传递的过程,在夏季运行时稳定、可靠。但把蒸发式冷凝器转换为蒸发器的冬季工况,由于蒸发式冷凝器换热管为光管以及喷淋水量有限,结构本身的特性决定了采暖工况的能效比(EER)小于1,这种转换没有实际的意义,也不经济。
Summer working condition of evaporative condenser is a process that has heating and mass transference and its working is stable and fixable. But in winter working condition of evaporative condenser is turned into evaporator. Its structure characteristic decides that its EER of heating is smaller than 1, for heat-exchange coil of evaporative condenser is smooth tubes and spray water is finite. This kind of conversion has no actual meaning and is not economical.
出处
《建筑热能通风空调》
2005年第5期64-67,共4页