期刊文献+

110 kV电缆终端头爆炸事故分析 被引量:20

Analysis of Explosion Accident of 110 kV Power Cable Termination
下载PDF
导出
摘要 为确定一110 kV电缆终端头爆炸事故原因,通过对事故情况调查、事故电缆终端头解剖、电缆和材料切片检查分析,认为电缆终端头预留的半导电层尺寸超过安装要求是电缆终端头爆炸事故的主要原因;最后提出了预防同类事故的相关建议。 In order to determine the reason of explosion of llOkV cable terminal, the investigation of accident and analysis of cable terminal and insulation is carried out. It is concluded that the main reason is that the semiconductive layer of cable terminal exceed the required dimension and the another reason is the installation of stress prick is not perfect.
出处 《高电压技术》 EI CAS CSCD 北大核心 2005年第11期74-75,共2页 High Voltage Engineering
关键词 电缆终端头 爆炸 事故分析 cable termination explosion accident analysis
  • 相关文献

参考文献3

  • 1GB/T11017.1-11017.3.额定电压110 kV交联聚乙烯绝缘电力电缆及附件[S].[S].,2002..
  • 2.[D].西安:西安交通大学,1975.
  • 3IEC60840. Power cables with extruded insulation and their accessories for rated voltages above 30 kV (Um=36 kV) up to 150 kV (Um=170 kV)-test methods and requirement[S], 2004.