期刊文献+

相控开关的最佳投切相位研究 被引量:37

Research on Optimum Switching Phase of Phasing Switches
下载PDF
导出
摘要 相控开关的核心问题之一是最佳投切相位的确定,而最佳投切相位又与断路器的预击穿绝缘特性密切相关。针对断路器预击穿特性对最佳同步关合目标相位的影响,文中引入了关合系数k,并对其进行分类讨论,详细分析了断路器合闸时的预击穿物理过程,同时考虑到断路器动作时间分散性,得到了不同绝缘强度下降率(RDDS)与机械分散性条件下的最佳投切相位计算公式。 One of the dominant factor in phase controlled switching is the determination of optimal switching phase, while the optimal switching phase is mainly affected by the pre-strike characteristics of the circuit breaker. According to the pre-strike phase associated with the mechanical scatters, the making factor k is introduced and discussed in classification, and the pre-strike physical process is analyzed in detail. The computing formulas of optimum switching phase are obtained as function of decrease rate of dielectric strength (RDDS) and mechanical scatters.
出处 《高压电器》 EI CAS CSCD 北大核心 2005年第6期408-411,共4页 High Voltage Apparatus
基金 自然科学基金项目(50107000)
关键词 相控开关 预击穿 绝缘强度下降率 最佳投切相位 phasing switch pre-strike
  • 相关文献

参考文献8

  • 1Delfino B, Fornari F, Gemme C, et al. Power Quality ImProvement in Transmission and Distribution Networks Via Synchronous Switching [J]. Transmission and Distribution Conference and Exposition, IEEE/PES, 2001, 19(28): 367-372.
  • 2Lee W Y, Park K Y,Chong J K, et al. A Method to Decide the Switching Instants of Controlled Switching Circuit Breaker for Shunt Reactors [J]. Transmission and Distribution Conference and Exhibition, 2002, 3(10): 1 760-1 765.
  • 3Kohyama H, Wada K, Hidaka M, et al. Development of550 kV and 362 kV Synchronous Switching Gas Circuit Breakers [A]. Transmission and Distribution Conference and Exposition[C], IEEE/PES, 2002(1): 597-602.
  • 4Cereda C, Gemme C, Reuber C. Synchronous Medium Voltage Circuit Breakers: ABB Solution Based on Magnetic Drive and Electronic Control [A]. CIRED 15th Conference on Electricity Distribution[C], Nice, CIRED, 1999.
  • 5丁富华,邹积岩,方春恩,段雄英.相控真空断路器投切空载变压器的应用研究[J].中国电机工程学报,2005,25(3):89-93. 被引量:68
  • 6钱家骊.相位控制高压断路器的动向[J].高压电器,2001,37(1):38-40. 被引量:35
  • 7Naik B R,Asche R G,Billings S,et al.Field Verification of Controlled Switching GCB[A].Power Engineering Society Summer Meeting[C],IEEE,2002(1):21-25.
  • 8Sun Peng, Konig D. Optimal Controlling of the Interruption of High Short Circuit Currents with A Monophase Vacuum Interrupter [A]. Proceedings of the 19th ISDEIV [C], Xi'an,2002(2): 427-430.

二级参考文献14

  • 1电力系统开关任务调查委员会.面向廿一世纪电力系统的开关任务(日文).电气学会技术报告[M].-,2000,3.774.
  • 2汤蕴瑶.电机学[M].北京:机械工业出版社,1981..
  • 3Ito H. Controlled switching technologies, state-of-the-art[A].Transmission and Distribution Conference and Exhibition[C].IEEE/PES, Asia Pacific, 2002, vol.2: 1455-1460.
  • 4Kohyama H, Wada K, Hidaka Met al. Development of 550kV and 362 kV synchronous switching gas circuit breakers[C]. Transmission and Distribution Conference and Exposition, IEEE/PES, 2001, 597-602.
  • 5Mahgoub O A. Microcontxoller-based switch for three-Phase transformer inrush current minimization[A]. Power Electronics Congress[C]. 1996: 107-112.
  • 6Brunke J H, Frohlich K J. Elimination of transformer inrush currents by contxolled switching[J]. IEEE Transactions on Power Delivery,2001, 16(2): 276-285.
  • 7Laszlo P, Gyorgy B, Gabor Bet al. Reducing the magnetizing inrush current by means of contxolled energization and de-energization of large power transformers[A]. International Conference on Power System Transients[C]. New Orleans, 2003.
  • 8Tsutada H, Hirai T, Kohyarna H, et al. Development of synchronous switching contxoller for gas circuit breakers[A]. Transmission and Distribution Conference and Exhibition[C]. Asia Pacific, 2002, vol.2:807-812.
  • 9付万安,宋宝韫.高压断路器永磁操动机构的研究[J].中国电机工程学报,2000,20(8):21-26. 被引量:70
  • 10林湘宁,刘沛,杨春明,刘世明.利用改进型波形相关法鉴别励磁涌流的研究[J].中国电机工程学报,2001,21(5):56-60. 被引量:57