摘要 讨论了线路杆塔工频接地电阻测量方法,通过现场用接地摇表法(三极法)和钳表法对不同地形、不同电压等级线路杆塔接地电阻测量对比,发现钳表法测量误差极大,且误差无规律可循,无法修正,必须引起同行们的高度重视。通过对比,认为三极法测量比较准确。 The methods to treasure power- frequency ground resistance of transmission line towers and poles have been discussed. Comparing the ground resistance measurements of different topographic position and different voltage level by using ground megger (3 - pole method) and clamp meter in the site, it is found that the measuring error of clamp meter is great and the error has no regular pattern to be followed and cannot be corrected, so much attention should be paid to these points. Through comparison, the measurernent of 3 - pole method is regarded as the more accurate one.
作者 杜洋 李龙江
机构地区 达州电业局
出处 《四川电力技术》 2005年第6期10-12,共3页 Sichuan Electric Power Technology
关键词 输电线路 杆塔 接地电阻 测量方法 transmission line tower and pole ground resistant measuring method