期刊文献+

对室内消火栓灭火系统栓口出水压力的探讨 被引量:3

Discussion on the Pressure of Indoor Hydrant System for Fire Protection Design of Tall Buildings
下载PDF
导出
摘要 通过对室内消火栓栓口出水压力的计算、分析,从理论上推导得出室内消火栓系统竖向分区的数值.对消火栓灭火过程进行了数据分析与计算,并结合我国消防人员实际体能和市场减压型消火栓生产情况,提出了对《高层民用建筑设计防火规范》(1999)第7.4.6.5条规定进行修改的建议:将该条规范中0.50 MPa降低为0.40 MPa,提高消火栓系统灭火的安全性、可靠性及合理性. Based on the computation and analysis of the hydrant exit water pressure in indoor hydrant system, this paper theoretically infers to the system vertical district value in the indoor hydrant system. According to the data analysis and the computation to fire-fighting hydrant system and the actual physical ahility of fire fighter and the production of decompression style indoor hydrant system in China, it is proposed that in the 7. 4. 6.5th of 《Code for Fire Protection Design of Tall Buildings》 ( GB 50045 - 95 ) ( 2001 ) the hydraulic pressure be reduced by from O. 50 MPa to 0. 40 MPa, to enhance indoor hydrant system fire fighting security, the reliability and the rationality.
出处 《桂林工学院学报》 CAS 北大核心 2005年第4期476-478,共3页 Journal of Guilin University of Technology
基金 国家自然科学基金青年基金资助项目(50409016) 中欧科技合作第五框架资助项目(ICA4-CT-2002-10004)
关键词 高层民用建筑设计防火规范 消火栓 栓口 出水压力 indoor hydrant export hydraulic pressure code decompression
  • 相关文献

参考文献4

二级参考文献6

  • 1-.建筑设计防火规范GBJ16-87修订版[M].中国计划出版社,1997..
  • 2-.高层民用建筑设计防火规范GB50045-95[M].中国计划出版社,1995..
  • 3-.采暖与卫生工程施工及验收规范GBJ242-82[M].中国计划出版社,1982..
  • 4建筑设计防火规范(GBJ16-87)(修订版),1997年
  • 5高层民用建筑设计防火规范(GB50045-95),1995年
  • 6采暖与卫生工程施工及验收规范(GBJ242-82),1982年

共引文献5

同被引文献4

引证文献3

二级引证文献1

相关作者