期刊文献+

安装固态短路限流器后距离保护整定的改进方法 被引量:12

Improved Setting Method of Distance Protection with the SSFCL
下载PDF
导出
摘要 故障限流器在电力系统中应用时将对继电保护尤其是距离保护产生一定的影响。以带旁路电感变压器耦合三相桥式固态限流器为例,详细分析了其对距离保护产生的影响,提出了一种应用于装设固态限流器线路的距离保护整定新方法,并通过仿真验证了所提出的方法可以有效消除限流器对距离保护的不利影响。 The fault current limiter (FCL) has certain impact on relaying protection, especially on distance protection, when applied in power systems. This paper studies the effect of the bridge type solid state fault current limiter (SSFCL) with bypass inductance on distance protection. An improved setting method of distance protection for the SSFCL-equipped transmission line is proposed. Simulation study further demonstrates that the proposed method can effectively eliminate the unwanted effect of SSFCL on distance protection.
出处 《电力系统自动化》 EI CSCD 北大核心 2006年第2期90-95,共6页 Automation of Electric Power Systems
关键词 电力系统 固态限流器 距离保护 整定 power systems SSFCL distance protection setting
  • 相关文献

参考文献4

  • 1HENRY S, BALDWIN T, STEURER M. The Effects of Fast Switching Fault Current Limiter on Distance Protection, In:Proceedings of the 35th Southeastern Symposium on System Theory. Morgantown (WV, USA): 2003. 2647-268.
  • 2张鹏飞,江道灼,刘华蕾.带旁路限流电感的新型固态限流器试验研究[J].电力系统自动化,2005,29(4):67-71. 被引量:17
  • 3李立群 柳占江 等.电力系统继电保护[M].水力电力出版社,1989..
  • 4LU Z, JIANG D, WU Z. A New Topology of Fault-current Limiter and Its Parameters Optimization. In:Proceedings of IEEE 34th Annual Conference on Power Electronics Specialists,Vol 1. Acapulco (NM, USA):2003. 462-465.