期刊文献+

带雨淋水膜的非耐热防火玻璃的火灾试验(英文) 被引量:2

Fire test on a non-heat-resistant fireproof glass with down-flowing water film
下载PDF
导出
摘要 研究了水膜对防火玻璃耐热性质的影响。用标准试验炉对门窗玻璃做火灾试验,温度高达1000℃。结果表明,对玻璃施用水膜能有效地经受试验的高温,水膜的蒸发潜热被用于保护建筑物的玻璃,免于因火灾造成融熔或炸裂。并且保留其完整性和绝缘性的试验时间由6min延长到100min。值得注意的是,玻璃表面的温度维持在90℃以下可持续100min。结论:用带水膜的防火玻璃替代通常装设的门是可行的。 The purpose of this study is to investigate the effects of a water film on the heat resistant property associated with the insulation of a fireproof glass. The evaporative latent heat of water film could be used to protect the glass of the building from melting or breaking as a fire occurs. In the experiment, the glass panes were fire-tested up to 1 000℃ by using a standard testing furnace for doors and windows. Results showed that the application of the water film on the glass pane could effectively resist the intensive heat from the burning in the test; and that the test period with permitted integrity and insulation could be extended from 6 minutes to 100 minutes. It was noted that the temperature of the glass surface could be kept under 90 ℃ for a 100-minute-test. The substitution of the fireproof glass with water film for the overhead door has been proven workable.
出处 《消防科学与技术》 CAS 2006年第1期89-96,共8页 Fire Science and Technology
关键词 水膜 耐热 防火玻璃 火灾试验 water film heat-resistant fireproof glass fire test
  • 相关文献

参考文献18

  • 1Technological Codes of the Building.79th Item of Building Design and Construction.Chinese Taipei,2004.
  • 2UL 10B,Standard for Fire Tests of Door Assemblies[S].Underwriter Laboratory Standards,2001.
  • 3Landau H G.Heat Conduction in a Melting Solid[J].Quarterly Applied Math,1950,8:312-319.
  • 4Carslaw H S and Jaeger J C.Conduction of Heat in Solid[J].Oxford University Press,UK,1959:510.
  • 5Sunderland T E and Grosh R J.Transient Temperature in a Melting Solid[J].J.Heat Transfer,1961,83:409-419.
  • 6Zien T F.Integral Solution of Ablation Problems with Time-dependent Heat Flux[J].AIAA J.,1978,16:1287-1295.
  • 7Thomas W C and Sunderland J E.Heat Transfer Between a Plane Surface and Air Containing Suspended Water Droplet[J].Ind.Eng.Chem.Fundam.,1970,9:369-374.
  • 8Aihara T,Taga M and Haraguchi T.Heat Transfer from a Uniform Heat Flux Wedge in Air-water Mist Flows[J].Int.J.Heat Mass Transfer,1979,22:51-60.
  • 9Chang C J,Lin T F and Yan W M.Natural Convection Flows in a Vertical Open Tube Resulting from Combined Buoyancy Effects of Thermal and Mass Diffusion[J].Int.J.Heat Mass Transfer,1986,29:1543-1552.
  • 10Yan W M.Liquid Film Vaporization on Natural Convection Heat and Mass Transfer in a Vertical Tube[J].The Canadian Journal of Chemical Engineering,1992,70:452-462.

同被引文献33

  • 1张庆义.受限空间火灾环境下玻璃破裂行为研究[D].合肥:中国科学技术大学,2006:6-24.
  • 2Emmons H W. Scientific progress on fire [J]. Ann Rev. Fluid Mechanics, 1980, 12:223-236.
  • 3Mai Y, L Jacob. Thermal stress fracture of solar control window panes caused by shading of incident radiation [ J]. Materials and Structures, 1980, 13(4): 283-288.
  • 4Yusc A, M Sano. Transition between Crack Patterns in Quenched Glass Plates[J]. Nature, 1993, 362(6418): 329 -331.
  • 5Yuse A, M Sano. Instabilities of quasi - static crack patterns in quenched glass plates [J]. Physica D, 1997, 108 (4): 365 -378.
  • 6Keski -Rahkonen O. Breaking of window glass close to fire [ J ]. Fire and Materials, 1988, 12(2) : 61 -69.
  • 7Emmons H W. Window Glass Breakage by Fire [ C ]//Home Fire Project Technical Report. Harvard University, 1988.
  • 8Pagni P J. Fire Physics - Promises problems, and Problems [ C ]//Fire Safety Science -Proeeedings of the Second International Symposimn, 1988.
  • 9Skelly M J, R J Roby, C L Beyler. Experimental investigation of glass breakage in compartment fires [ J]. Journal of Fire Protection Engineering, 1991, 3(1): 25-34.
  • 10Xie Q Y, Zhang H P, Wan Y T, et ah Full- scale experimental study on crack and tallout of toughened glass with different thicknesses [J]. Fire and Materials, 2008. 32 (5): 293 - 306.