摘要 针对110 kV电网联络线上中间变电站失压时,原有变电站备自投装置无法发挥作用的情况,研究了一种利用已有光纤通信通道传递运行状态信息、故障信息和跳合闸命令方式的备用电源自投方案。通过改进原有备自投装置的原理及逻辑,加装通讯接口和光通讯模块,实现与光纤网的接口。经在某城区110 kV电网中的应用与实施,较好地实现了多级串联电网远方备用电源自投。 When the center transformer substation no-voltage in 110 kV network tie-line, the reserve power of original substation cannot operate. A new reserve power scheme is put forward based on state information, fault information and on-or-off switch mode of present-used optical-fiber communication channel. The new scheme improves the old device's operation theory and logic by adding communication interface and optic communication module to be connected with optic-fiber-network. The scheme has been employed in 110 kV network to implement far-away reserve power of multi-level series network.
作者 唐海军
机构地区 常德电业局
出处 《继电器》 CSCD 北大核心 2006年第4期80-82,85,共4页 Relay
关键词 备自投 故障检测 光纤通道 远方实现 reserve power fault test optical-fiber channel far-away implementation