摘要 本设计为金华华都大厦的空调系统及防排烟设计,工程位于金华市,共18层,其中地下两层,地上十六层,建筑面积18800平方米.夏季冷负荷为1971.5 kw,冬季热负荷为1106 kw.空调系统采用冷暖两用,采用一次泵,分四个区.小空间采用风机盘管加独立新风系统,风机盘管一律吊顶卧式暗装,卫生间排风,新风负荷由吊挂式空气处理机组承担;大空间采用全空气系统,新回风混合后经机组直接向房间供冷.防排烟采用消防楼梯间正压送风,地下室设备房设置防排烟系统,采用同一个系统,选用双速风机,平时排风,发生火灾时排烟. This is a design for air- conditioning system, defending and exhausting smoke system in Jinhua,include 18 layers,2 layers under the ground, 16 layers on the groundling with a construction area of 18800 square meters. The biggest load in summer is 1971.5KW, and in winter is 1106KW.The air conditioning is dual- purpose,adopting the pump once, controlling the return water and divided into four districts. Air blower serpentine independent new air system is adopted in small rooms, which is hung horizontally and secretly, and the air goes out from bathroom;The big rooms adopt the whole air system, fresh and recirculation air mix and pass through the aircrew, then sent to the room. The defending and exhausting smoke system is blown to press;The basement equipment room adopts the same system to exhaust air and smoke and choose the dualwind velocity fans. Ordinarily, it only exhausts air, and unless the fire disaster happened it doesnot exhaust smoke.
出处 《南华大学学报(自然科学版)》 2005年第F09期23-27,共5页 Journal of University of South China:Science and Technology
关键词 负荷 空气调节 防排烟 load air - conditioning defend and arrange smoke
  • 相关文献

参考文献8

  • 1GB50019-2003.采暖通风与空调设计规范[S].[S].,..
  • 2GB50045-95.高层民用建筑设计防火规范[S].[S].,2001年版..
  • 3朱霖.暖通空调常用数据手册[M].北京:中国建筑工业出版社,2002..
  • 4陈沛霖 岳孝方.空调与制冷技术手册[M].上海:同济大学出版社,1991..
  • 5陆耀庆.实用供热空调设计手册[M].北京:中国建筑工业出版社,2000..
  • 6JGJ26-95.民用建筑节能设计标准[S].[S].,2000..
  • 7路延魁.空气调节设计手册[M].北京:中国建筑工业出版社,2000..
  • 8伍小亭.风机盘管选型及系统设计中的一些问题[J].暖通空调,2000,30(4):46-48. 被引量:16

二级参考文献1

共引文献93

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部