期刊文献+

牵引变电所地网腐蚀与改造研究 被引量:4

Study on Reconstruction of Eroded Grounding Grid of Traction Substation
下载PDF
导出
摘要 牵引变电所地网是安全供电的重要设施。牵引变电所地网改造受场地限制,必须仔细设计才能够使接地电阻达到要求。本文根据实际情况,提出了以多根垂直接地极并联为主,采用等效扩大接地导体尺寸,延伸辅助地网的办法进行改造。经工程实践表明,该方法实用可行。 Grounding grid, a very important facility for safer power supply, will be eroded in different degree after running more than ten years. The grounding resistance will increase and endanger personnel's safety. Since its reconstruction will be constrained by the site space, so the prudential design is needed so as to reach the required grounding resistance. In connection with actual requirements, the paper puts forward the reconstruction of grounding grid by erection of upright grounding poles, most of which are set in parallel, enlarging the dimensions of equivalent conductors and expanding the auxiliary grounding grid. Its applications in the projects show that it is practical and feasible.
出处 《电气化铁道》 2006年第1期16-18,共3页 Electric Railway
关键词 牵引变电所 接地网 改造 接地电阻 traction substation grounding grid Rebuilding grounding resistance
  • 相关文献

参考文献3

  • 1DL/T 621-1997.交流电气装置的接地[S],1997.
  • 2TB 10208-1998.铁路电力牵引供电施工规范[S],1998.
  • 3TB 10009-2005.铁路电力牵引供电设计规范[S],2005.