开式膨胀水箱热水供暖系统补水崩片和补水缓慢的分析及控制

Causes for radiator break and overlong water making-up time in the heating system with an open tank and their countermeasures
下载PDF
导出
摘要 探讨了开式膨胀水箱热水供暖系统补水崩片和补水缓慢的原因,提出了控制措施,并以工程实例介绍了控制效果。 In view of the fact that in the hot water heating system with an open expansion tank,some radiators break during water making-up and it takes much longer than expected to make up water to the system,analyses the causes and gives a solution involving resetting the location of the neutral point in the system and adjusting the size of the expansion pipe so as to control the make-up water flow rate equal to or higher than that required by the tank.Gives an example to demonstrate the effects of the solution.
出处 《暖通空调》 北大核心 1996年第5期77-79,共3页 Heating Ventilating & Air Conditioning
关键词 热水采暖 供热 开式膨胀水箱 补水 崩片 控制 hot water heating system open expansion tank make up water radiator break constant pressure point countermeasure