期刊文献+

玻璃绝缘子在浙江省500kV电网的运行概况 被引量:2

The General Situation of Domestic Glass Insulators Used on 500 kV Electrical System in Zhejiang Province
下载PDF
导出
摘要 介绍了玻璃绝缘子在浙江省500kV电网的运行情况,按照相关标准对自破玻璃绝缘子的残锤和同串未自破的LXHY3-160型产品进行测试,结果表明,自破后的机械破坏负荷依然达到要求,同串LXHY3-160型产品也均达到要求。玻璃绝缘子在浙江省500kV电网的运行分析表明:玻璃绝缘子在运行初期(1~2年),其自破率偏高,尔后逐年呈下降趋势并稳定在一定水平上;每年7~9月,玻璃绝缘子自破率高于其他月份;耐张串上的玻璃绝缘子的自破率高于直线串;从多条输电线路运行电压的升高情况来看,产品的自破率未见明显上升。 The general situation of domestic glass insulators used on 500kV electrical system in Zhejiang province was introduced. Mechanical tests were made on residua of self-shattered insulator of LXHY3-160 type and sound insulators taken from the same string according relevant standard showed satisfactory strength of both insulator residua and sound insulators. Service evaluation on glass insulators at 500kV system in Zhejiang province showed a higher self-shatterlng rate at beginning (1- 2years) July-Se and lowered down progressively in following years and then stabilized at certain level. During ptember, every year the self-shattering rate was higher then in other months, which on tensile string higher then on vertical string. A higher self-shattering not observed at a few transmission lines with enhanced operating voltage.
作者 吴健 顾洪连
出处 《电瓷避雷器》 CAS 2006年第2期24-25,31,共3页 Insulators and Surge Arresters
关键词 玻璃绝缘子 零值自破 雷击闪络 glass insulator self-shattering lightning flashover
  • 相关文献

参考文献3

  • 1南京电气集团公司.钢化玻璃绝缘子技术资料汇编[M].南京:南京电气集团公司,1996.
  • 2顾洪连,孙泽慧.玻璃绝缘子运行特性分析[J].电力建设,2000,21(11):48-50. 被引量:16
  • 3南京电气集团公司质检部.LXHY3-160玻璃绝缘子的机电性能试验报告[R].南京:南京电气集团公司,2005.

二级参考文献1

共引文献15

同被引文献28

引证文献2

二级引证文献17