期刊文献+

变压器局部放电综合判断分析 被引量:10

Comprehensive Judgement Analysis about Partial Discharge in Transformer
下载PDF
导出
摘要 指出了变压器局部放电定位的重要性,简述了多端子测量多端子校正、变电位多端测量、脉冲极性鉴定法和超声波定位法的原理,通过实例分析了局部放电定位过程和处理方法, 并得出要根据产品的不同结构和类型,灵活选择不同的方法, 且相互验证,互为补充,才能较准确地进行局放定位的结论。 The paper has pointed out the importance of partial discharge location in transformer. The principles of multiple terminals measurement and calibration, variable voltage multiple terminals measurement, pulse polarity differentiation, and partial discharge location based on ultrasonic are sketched. Through an example, the location process and treatment method of partial discharge are analyzed. In order to locate the partial discharge more accurately, it should be made to choose different methods flexibly according to different structuer and type of the transformer, and to make cpmperhensive analysis.
作者 葛为民
机构地区 常州工学院
出处 《高压电器》 CAS CSCD 北大核心 2006年第2期144-145,148,共3页 High Voltage Apparatus
关键词 变压器 局部放电 NIT 定位分析 transformer partial discharge measurement location analysis
  • 相关文献

参考文献1

  • 1胡启凡 曹利安 谢毓城.变压器试验技术[M].北京:机械工业出版社,2001,24(8).62-64.

共引文献2

同被引文献97

引证文献10

二级引证文献48