太原地区110kV网中变压器中性点保护 被引量:2

Superficial Talk on 110 kV Transformer Neutral-point Protection in Taiyuan Area
下载PDF
导出
摘要 针对太原电网110 kV辐射性网络中,变压器中性点的接地情况,分析线路末端发生单相接地故障,导致线末变压器中性点保护动作及所接母线上的线路保护反向动作的问题,通过对变压器中性点过电压现象的分析及对目前太原网变压器中性点采用的保护配置方式进行了探讨,提出了适合太原电网现行变压器中性点保护的配合与整定的建议。 Regarding situation of transformer netual-point earthing in 110 - radiate network, It analysed single earthing faults which occurred at the end of line, result in transformer netual protection acting and reacting of its line protection on the bus bar. Through analyzing of transformer neutral-point over-voltage, It discussed protection scheme of transtormer netrualpoint in Taiyuan power network, put forward advice of its assortment and acting value.
出处 《山西电力》 2006年第2期19-22,共4页 Shanxi Electric Power
关键词 中性点 过电压 系统分析 保护措施 netual-point overvoltage system analyzing protection measure
  • 相关文献

同被引文献17

  • 1孙亮,孙晨.中性点接地方式及接地故障分析[J].林业科技情报,2004,36(2):54-54. 被引量:1
  • 2董梅.110kV分级绝缘变压器中性点的过电压保护[J].江苏电机工程,2005,24(4):62-64. 被引量:2
  • 3秦家远,阮江军.变压器中性点过电压保护综述[J].华中电力,2006,19(1):17-20. 被引量:25
  • 4DL/T620-1997.交流电气装置的过电压保护和绝缘配合[S].[S].,..
  • 5解广润.电力系统过电压[M].北京:水利电力出版社,1988..
  • 6陈维贤.电网过电压教程[M].北京:中国电力出版社,1999..
  • 7SD 325-1989,电力系统电压和无功电力技术导则(试行)[S].
  • 8刘星.宁夏电网110~220kV主变中性点保护研究[D].武汉:武汉大学,2008.
  • 9Owen E L.The historical development of neutral grounding practices[J].Industry Applications Maga-zine,IEEE,1997,3(2):10121416-10121820.
  • 10David Shipp,Frank Angelini.Characteristics of dif-ferent power systems neutral grounding techniques:facts and fiction[C] //Pulp and Paper Industry Tech-nical Conference,Conference Record of1990Annual,1990:107-116.

引证文献2

二级引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部