摘要
某冷水机组冷凝器在短时间使用后铜翅片管发生泄漏。通过现场的外观检查,并对管试样进行宏观、微观分析,以及对垢物的能谱和X射线衍射分析,结果表明:翅片管泄漏的原因是管内沉积物导致缝隙腐蚀引起的管材穿孔。
After a short period of running, leakage occurred in the copper fin tube of a water cooled screw chiller. By the on site appearance inspection, macro and micro morphological analysis to tube specimen, electron spectrometry analysis and X - ray diffraction to scale, the result indicates that the perforation of the fin tube was caused by the crevice corrosion under the deposit, it leads to the leakage.
出处
《压力容器》
北大核心
2006年第4期44-46,共3页
Pressure Vessel Technology
关键词
冷凝器
翅片管
泄漏
缝隙腐蚀
condenser
fin tube
leakage
crevice corrosion