隔离病房隔离效果的研究(3) 被引量:6

Study on isolation effects of isolation wards (3)
下载PDF
导出
摘要 基于大气尘实验,研究了隔离病房开门时温差对污染物外泄的作用.结果显示,温差作用是一般压差作用抵消不了的;2℃温差时污染物交换量比0℃温差时增加50%左右;缓冲室可对温差作用引起的污染物交换起到15~30倍的动态隔离作用. Based on the atmospheric dust experiment, researches the contaminant air exchange caused by the temperature difference while opening the door of isolation wards. Concludes that the undesired effect of temperature difference could not be eliminated just by the negative pressure difference between adjacent rooms, that the contaminant air exchange would increase about 50% in the temperature difference of 2℃ than that in the temperature difference of 0℃, and that such contamination could be reduced to about 1/31~1/16 with the helo of buffer rooms.
出处 《暖通空调》 北大核心 2006年第5期1-4,共4页 Heating Ventilating & Air Conditioning
关键词 隔离病 房隔离效果 温差 大气尘 缓冲室 isolation ward, isolation effect, temperature difference, atmospheric dust, buffer room
  • 相关文献

参考文献8

  • 1许钟麟 张益昭 王清勤.关于负压隔离病房缓冲室的作用[J].建筑科学,2005,21:52-56.
  • 2许钟麟,张益昭,王清勤,刘华,温风,冯昕,于玺华,赵力,王荣,张彦国,牛维乐,易新文,欧燕川,卢伟明.关于隔离病房隔离原理的探讨[J].暖通空调,2006,36(1):1-7. 被引量:28
  • 3冯昕,许钟麟,张益昭,王清勤,刘华,温风,于玺华,赵力,王荣,张彦国,牛维乐,易新文,欧燕川,卢伟明.负压隔离病房气流组织效果的数值模拟及影响因素分析[J].建筑科学,2006,22(1):35-41. 被引量:13
  • 4许钟麟,张益昭,王清勤,温风,刘华,赵力,冯昕,张彦国,王荣,牛维乐,狄彦强,于玺华,易新文,欧燕川,卢伟明.隔离病房隔离效果的研究(1)[J].暖通空调,2006,36(3):1-9. 被引量:16
  • 5许钟麟,张益昭,王清勤,温风,刘华,赵力,冯昕,张彦国,王荣,牛维乐,狄彦强,姚丹,于玺华,易新文,欧燕川,卢伟明.隔离病房隔离效果的研究(2)[J].暖通空调,2006,36(4):1-4. 被引量:8
  • 6CDC.Guidelines for Preventing the Transmission of Mycobacterium Tuberculosis in Health Care Facilities[G],1994
  • 7ASHRAE.ASHRAE Handbook-HVAC Application[G],1991
  • 8Ole Christian Ruge,Hilde B(a)nrud,Oddvar Bjordal.Ultraviolet Technology and Intelligent Pressure Control Solutions Jointly Provide True Isolation Rooms for Infectious Patients[C]//Klean ASA,2002

二级参考文献11

  • 1沈晋明.多用途隔离病房和无凝水空调技术[J].建筑热能通风空调,2005,24(3):22-26. 被引量:20
  • 2许钟麟,张益昭,王清勤,温风,刘华,赵力,冯昕,张彦国,王荣,牛维乐,狄彦强,于玺华,易新文,欧燕川,卢伟明.隔离病房隔离效果的研究(1)[J].暖通空调,2006,36(3):1-9. 被引量:16
  • 3冯昕,许钟麟,张益昭,王清勤,刘华,温风,于玺华,赵力,王荣,张彦国,牛维乐,易新文,欧燕川,卢伟明.负压隔离病房气流组织效果的数值模拟及影响因素分析[J].建筑科学,2006,22(1):35-41. 被引量:13
  • 4许钟麟.空气洁净技术原理3版[M].北京:科学出版社,2004..
  • 5CDC.Guidelines for Preventing the Transmission of Mycobacterium Tuberculosis in Health-care Facilities[M],1994.
  • 6Wolfe H W,Harris M H,Hall L B.Open operating room doors and staphylococcns aureus[M],1981.
  • 7.李书云 展素萍等人2004年测定[Z].,..
  • 8.李书云、展素萍等人2004年2月测定[Z].,..
  • 9Qingyan Chen,Jelena Srebric.simplified diffuser boundary conditions for numerical room airflow models[R].ASHRAE RP-1009 research report,March 20,2001.
  • 10WHO Western Pacific Regional Office,interim guidelines for national SARS preparedness[R].revised May 26,2003.

共引文献42

同被引文献15

引证文献6

二级引证文献11

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部