华东电网500 kV任上5237线飑线风致倒塔事故调查分析 被引量:114

Investigation on Tower Collapses of 500 kV Renshang 5237 Transmission Line Caused by Downburst
下载PDF
导出
摘要 强风暴是对输电线路威胁最大的一种自然灾害,强风暴导致的高压输电线路和输电塔破坏的事故时有发生。作者首先介绍了华东电网500 kV任上5237线飑线风致10基输电塔连续倒塔事故的现场调查结果,按照输电塔倒塔的严重程度对杆塔进行了分类;分析了飑线风的破坏特性及其对输电线路的危害。对输电塔倒塔的原因进行初步分析后认为: 特大飑线风是造成这次输电塔倒塔的主要原因;输电塔抗风设计规程中横隔面的布置数量不足,导线与输电塔之间的风动力耦联作用也不容忽略。 In all kinds of natural disasters jeopardizing transmission lines, intense storm is the most minatory one, the accidents and failures in high voltage transmission lines and the damage to transmission towers caused by intense storm occur now and then. The authors firstly present the result of field investigation on the failures that ten towers of 500kV Renshang transmission line 5237 collapsed and the flashover of 500kV Renshang lines 5237 and 5238 of East China power grid occurred, those failures were caused by the downburst which hit Siyang County, Jiangsu province on June 14th, 2005. According to the order of severity of transmission tower collapse, the collapsed towers are classified; the destruction characteristic of downburst and its damage to transmission lines are analyzed. The results of preliminary analysis on the reasons of tower collapses show that the extraordinarily intensive downburst is the principal cause of these failures; the quantity of diaphragms designed according to the current design specification for transmission towers to resist wind is insufficient and the dynamic coupling effects between transmission towers and conductors cannot be neglected.
出处 《电网技术》 EI CSCD 北大核心 2006年第10期59-63,89,共6页 Power System Technology
基金 国家自然科学基金资助项目(50508026) 国家自然科学基金委优秀创新研究群体科学基金资助项目(50321803)。~~
关键词 输电线路 飑线风 输电塔倒塔 现场调查 横隔面 输配电工程 transmission lines downburst tower collapses field investigation diaphragm transmission anddistribution
  • 相关文献

参考文献26

二级参考文献65

共引文献857

同被引文献1125

引证文献114

二级引证文献1003

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部