医院高层建筑中医护办公室空气质量分析

Air Analysis of the doctor-nurse office in high building of hospital
原文传递
导出
摘要 对中国医科大学第一医院14层建筑内的6、7层同侧病区的医护办公室进行了O2、PO2、CO2、细菌总数的检测。结果可见:被检测的医护办公室O2、PO2符合国家室内标准的正常范围;细菌学检测平均值高于卫生部提出的普通病室内<500CFU/m3的标准;C02检测平均值在0.07%以下,但在上午8:30检测中有时CO2超过0.07%的标准,细菌总数亦偏高,应引起足够重视。 O2,PO2,CO2,total number of bacteria were detected in doctor-nurse offices which are at the same side on the 6 and 7th floor in the first affiliated hospital of China Medical University. The results showed that the detected O2 and PO2 in doctor-nurse office were conformed to the normal range of country's indoor standard. The average value of bacteria detection was above the standard Which is less than 500/m3 in ordinary ward given by the Ministry of Health of China. The average CO2 detection was below 0.07% ,but sometimes above 0.07% during the 8:30 detection in the morning ,total number of bacteria was a little higher too,which suggested that more attention are needed.
出处 《中华护理杂志》 CSCD 北大核心 1996年第4期193-196,共4页 Chinese Journal of Nursing
关键词 医院 高层建筑 医护办公室 空气质量 High building Doctor-nurse office Air quality