R22和R134a应用于家用热泵热水器实验性能研究 被引量:14

The Research on the Character of R22 and R134a Applied in Household Heat Pump Water Heater
下载PDF
导出
摘要 本实验分别用R22和R134a作为家用热泵热水器的制冷工质,对比分析讨论和实验研究了其加热效果和性能系数,结果表明:R134a系统将90L来流水加热到50℃需要多于实验R22热泵热水器系统40min;相同的加热时间,R134a系统水箱内底层温度和表层温度都低于R22系统,两种系统相同位置的温差随着水箱内温度的提升而增大;R22系统COP高于R134a系统23.1%,这为家用热泵热水器系统制冷工质的选择提供参考。 Refrigerating medium R22 and R134a are applied in household heat pump water heater in this experiment. The heating result and COP are researched and discussed by contrast. The experiment results show that it need more 40min in use of the R134a system than R22 system in order to heat the inlet water to 50℃, the water temperatures of R134a system at the bottom and in the surface are lower than that of R22 system in the same heating time, the temperature increases as the water temperature increases between the two system in the same situation and the COP of R22 system is higher than the COP of R134a system. It can provide reference on the choice of refrigerating medium in the household heat pump water heater.
出处 《广东化工》 CAS 2006年第6期25-27,共3页 Guangdong Chemical Industry
关键词 R22 R134A 热泵热水器 R22 R134a heat pump water heater
  • 相关文献

参考文献3

二级参考文献6

  • 1董天禄.离心式/螺杆式制冷机组及应用[M].北京:机械工业出版社,2001.177-198.
  • 2National Institute of Standards and Technology.NIST Thermodynamic Properties of Refrigerants and Refrigerant Mixtures Database (REFPROP) [R],1996.
  • 3Radermacher R,Jung D S.Theoretical analysis of replacement refrigerants for R22 for residential uses[G]//ASHRAE Trans,1993,99(1):333- 343.
  • 4Mulroy W,Kauffeld M,Mclinden M,et al.Experimental evaluation of two refrigerants mixtures in a breadboard air conditioner [C] // Proc of Int Refrigeration,Purdue Conference on CFCs,1988:27- 34.
  • 5谷波,李文华.R22三种替代物R134a、R410a和R407c在空调系统中性能对比研究[J].流体机械,1999,27(10):41-42. 被引量:26
  • 6曹锋,陈芝久,赵薰,黄培炫,李汉武.制冷系统中R407C替代R22技术研究综述[J].制冷与空调,2002,2(1):61-63. 被引量:18

共引文献10

同被引文献86

引证文献14

二级引证文献78

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部