VLF电压试验电压幅值与试验时间的优选 被引量:4

Optimizing Validation of Voltage and Time for VLF(0.1Hz) Voltage Testing
下载PDF
导出
摘要 VLF电压试验电压(UT)和试验时间(tT)的选取直接影响到有效地发现绝缘缺陷的概率,但目前电力电缆线路VLF电压试验时如何选取UT和tT仍无明确结论。1980年以来各国标准规定值差异很大,试验的有效性和等效性尚在探讨之中,目前一般取UT=2~3.5U0(U0为相电压),tT=15~60min。长期积累的运行经验和理论及试验研究证实,延长tT和提高UT将对电缆介质造成不可逆损害,导致介质早期击穿。因此结合国内外现场和试验室研究结果并采用数理统计分析的方法优选了VLF(0.1 Hz)UT和tT。结果表明:UT=3U0时,tT取40min,基本能够满足电力电缆线路绝缘品质判别的现场试验要求。 VLF (0.1Hz) voltage test as one of the quality evaluation methods has been applied to medium voltage capacitive equipments, i.e. electrical generators, electrical motors and power cable lines for more than 20 years. Until today, it has been disputed that how to validate the test time and test voltage when taking VLF voltage test on power cable line because the different probability of identifying faults hidden in dielectric in advance by the test effectively. The validity and equivalence of these test results have been researched and discussed since 1980's. Unfortunately, the test results are not obvious evidence. In fact, the technical standards of VLF voltage test including test voltage range from 2U0 up to 3.5 U0 and test time range from 15 min up to 60 min are confirmed by different countries in the word. Practice experience in field and many results of theoretical research as well as parallel tests in laboratory in China have proved that extending test time and increasing high voltage are not necessary and very harmful to dielectric of power cable due to the power cable using high resistive solid dielectric. Even the damage of power cable dielectric is not rehabilitated and lead power cable line early or unexpected broken. Therefore, it is important to optimize the combination of test time and test voltage of VLF (0.1Hz) voltage test today. For optimizing validation of test voltage and test time, the validity and equivalence as well as relation of test voltage and test time of VLF (0.1Hz) voltage test is discussed and analyzed in detailed by mathematic statistics based on a mass of test experience in field and in laboratory in this paper. The results of research and optimization in the paper prove and verify that the test method of 3U0 test voltage and 40min test time is much better fit for power cable lines in field test, and may meet the estimation of dielectric quality of power cable lines on-site testing.
出处 《高电压技术》 EI CAS CSCD 北大核心 2006年第6期18-20,共3页 High Voltage Engineering
关键词 VLF试验 电力电缆 优化 试验电压 试验时间 VLF Test Power Cable Optimization Test Voltage Test Time
  • 相关文献

参考文献16

  • 1罗俊华,马翠姣,邱毓昌,金祎,陈守直,史济康.35kV及以下XLPE电力电缆试验方法的研究[J].电网技术,2000,24(12):58-61. 被引量:61
  • 2彭潜,陈俊武,梁望霖,吴云飞,袁皓.XLPE电缆工频耐压试验探讨[J].高电压技术,2005,31(5):55-55. 被引量:14
  • 3柳淑艳,杨帆.0.1Hz超低频正弦波耐压试验技术及应用[J].高电压技术,2004,30(z1):79-80. 被引量:20
  • 4罗俊华,杨黎明,史济康,朱海钢.电力电缆及试验技术回顾[J].高电压技术,2004,30(z1):81-82. 被引量:49
  • 5Eager G S. High voltage VLF testing of power cables [J]. IEEE Transactions on Delivery, 1997,12(2) : 565-670.
  • 6Hans R.Generlic. Field testing of HV power cables: VLF testing [J].IEE Electrical Insulation Magazine, 11(5): 22-24.
  • 7Baur M, Mohaupt P, Schlick T. New results in medium voltage cable assessment using very low freguancy with partical discharge and dissipation factor measurement[C]. CIGRED 17th International Conference on Electricity Distribution. Barcelona, 2003.
  • 8IEEE P400.2/D5. Guide for field testing of shielded power cable systems using very low frequency(VLF)[S]. 2000.
  • 9CENELEC HD620S1. Distribution cables with extruded insulation for rated voltages from 3.6/6(7.2)kV to 20.8/36(42)kV [S]. 1996.
  • 10中国华北电力集团公司文件.关于印发华北电力集团公司《电力设备交接和预防性试验规程》2002修订本的通知[S].北京:华北电力集团,2002.

二级参考文献11

共引文献349

同被引文献44

引证文献4

二级引证文献24

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部