摘要
对韶关发电厂200 MW机组高压加热器(高加)投入率偏低的原因进行了分析,认为高加投入不当,注水速度太快,投入不及时,焊接质量差,管壁积垢热阻增加等是主要原因。提出了提高高加投入率的改进措施,实行后取得了较好效果。
The causes leading to somewhat low rate of putting highpressure heater into service for 200 MW units in Shaoguan Power Plant, Guangdong Province,have been analysed.It is believed that the main causes to be as follows: improperly putting the highpressure heater into service;rapid speed of water injection;not timely putting into service;bad quality of welding;scaling on the wall of tubes;and increase of thermal resistance etc..For these,corresponding retrofit measures for enhancing the rate of putting highpressure heater into service have been put forward,and the results obtained after implementation of said measures being presented.
出处
《热力发电》
CAS
北大核心
2006年第5期38-39,43,共3页
Thermal Power Generation
关键词
200
MW机组
高压加热器
泄漏
高加投入率
温升率
温降率
换热
200 MW unit
high-pressure heater
leakage
rate of putting high-pressure heater into service
temperature rise rate
temperature drop rate
heat exchange