公共场所中央空调系统军团菌污染环节的研究 被引量:5

STUDIES ON THE LINKS OF LEGIONELLA CONTAMINATION IN CENTER AIR CONDITIONING SYSTEM IN PUBLIC PLACES.
下载PDF
导出
摘要 目的:探索中央空调系统中各环节军团菌的污染情况和可能的污染环节。方法:对26户商场、宾馆、办公楼、医院等公共场所中央空调系统的冷却塔、冷凝器、膨胀水箱、蒸发器、冷凝水、空调送风末端等各环节点采集水样、涂抹样,检测军团菌。结果:135份中央空调系统各环节点,军团菌总检出率50.4%,分离到75株嗜肺军团菌,血清分型有Lp1和Lp10两种,水冷式、风冷式系统的阳性率分别为50.9%、47.8%,冷凝器水检出率高达93.8%,冷却塔水、膨胀水箱水在60%以上,低温运行的蒸发器水中检出率为40%,冷凝水为17.4%,97.1%的阳性水样中每ml水样中军团菌数小于100个。结论:各场所、各类型中央空调系统的各积、储水环节军团菌污染严重,军团菌有着顽强的低温生存能力,受军团菌污染的膨胀水箱水、冷冻水、冷却水、冷凝水都有可能对人体造成危害。 Objective: To describe and to explore the present status and approach of Legionella contamination in center air condition system. Methods: 135 samples were obtained from 26 public places such as markets, hotels, office buildings etc. Legionella was tested in water and painting samples of all components from cooling tower, condenser, swelling water box, evaporator, condensed water and blast terminal of center air condition in these pubilc places. Results: The total positive rate of Legionella was 50.4%, including two types of serogroup (Lp1 and Lp10) among these 75 strains of Pneumophila LegioneUa. The positive rates were 50.9%, 47.8% in water- cooling type systems and wind - cooling type systems respectively. The positive rate was 93.8% in condenser, and that was over 60% in cooling tower and in swelling water box. The positive rate was 40% in evaporator during lower temperature and 17.4% in condensed water. The amounts of Legionella were less than 100 per milliliter in 97.1% of the positive water samples. Conclusion: This study suggested that the Legionella contamination in the collection and storage components of center air conditioning system in public places is a very critical problem in our country. Legionella could survive in lower temperature, so it was possible that the population will be infected by Legionella from water of swelling water box, freezing water, cooling water and condenser water.
出处 《现代预防医学》 CAS 北大核心 2006年第8期1325-1327,1332,共4页 Modern Preventive Medicine
基金 马鞍山市级科技计划资助项目(2004-11)
关键词 空调系统 军团菌 污染 Air conditioning system Legionella Contamination
  • 相关文献

参考文献17

二级参考文献43

  • 1陈长怡,徐建新.军团病实验诊断方法进展[J].临床肺科杂志,1999,4(4):236-237. 被引量:2
  • 2魏婉江,谢 子,郭淑清,王桂琴,薛有忠,樊卫平,王根维,王洪涛.山西水环境军团菌分布及生物学特性研究[J].中国微生态学杂志,1994,6(6):1-6. 被引量:2
  • 3陈悦.军团菌实验室快速诊断技术的建立[J].上海预防医学,1999,11(9):398-400. 被引量:9
  • 4万超群 于恩庶 等.军团病.新发现的传染病[M].福州:福建教育出版社,1997.197-217.
  • 5赵季文 徐萃瑜 等.微量凝集试验在军团病流行病学调查中的应用[J].中华流行病学杂志,1986,7:209-211.
  • 6[1]卫生部法监司.公共场所集中空调通风系统卫生规范[S].2003.
  • 7[4]Edelstein PH, Meyer RD. Community outbreak of Legionnaires' disease [J]. Chest, 1998,85:114-120.
  • 8[5]Bhopal R. Source of infection for sporadic Legionnaires' disease:a review [J] .J Infect, 1995,320:9-12.
  • 9[6]Keller DW. An investigation confirming the potential for cooling towers to transmit Legionella species[J]. Clin Infect Dis, 1996,22:257-261.
  • 10[8]McCall E, Stout JE, Efficacy of biocides against biofilm-associated Legionella in a model system[A]. Proceedings of the 60th Annual Meeting,Intemational Water Conference[C]. Pittsburgh, USA, 1999,141-147.

共引文献224

同被引文献32

引证文献5

二级引证文献20

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部