摘要
结合工程实例,对风冷热泵+燃气调峰锅炉与水冷冷水机组+燃气热水锅炉这两种冷热源方案的经济性进行了比较。风冷热泵+燃气调峰锅炉方案虽然在目前的工程应用中的经济性较差,而且对于水资源相对充足的地区风冷热泵不占有优势,但从长远来看,风冷热泵具有巨大的潜力。随着我国大制冷量风冷热泵的研制、生产技术成熟,必然会改变由于购买国外机组导致的系统造价较高的情况。
The economy of two schemes of cooling and heat sources, including air-cooled neat pump plus gas peak-shaving boiler and water cooled chiller plus gas hot water boiler is compared by means of engineering example. Although the scheme of air-cooled heat pump plus gas peak-shaving boiler has a poorer economy in present engineering application, and the air-cooled heat pump is not dominant in the regions with relatively abundant water resource, but the potential of air-cooled heat pump is great in the long run. The situation of high cost of the system caused by purchasing foreign machine will be changed with the development of air-cooled heat pump with large refrigerating capacity in China and the maturity of productive technology.
出处
《煤气与热力》
2006年第8期42-44,共3页
Gas & Heat
关键词
风冷热泵
水冷冷水机组
经济性分析
建筑冷热源
air-cooled heat pump
water cooled chiller
economic analysis
building cooling and heat sources