期刊文献+

偏移阻抗继电器的整定计算及与方向阻抗继电器的比较

Setting Calculation of Deviation Resistance Relay and its Comparison with Direction Resistance Relay
下载PDF
导出
摘要 由于在偏移阻抗继电器的应用中,存在用方向阻抗继电器的整定计算代替偏移阻抗继电器的整定现象,本文给出1种偏移阻抗继电器的整定计算方法,并说明若用方向阻抗继电器的整定计算代替偏移阻抗继电器的整定计算,在某些情况下,将带来很大的误差。结论是:一般情况下是不能代替的。 In the application of deviation resistance relay, during the process of setting calculation, deviation resistance relay is replaced by direction resistance relay, occasionally. The paper provides a way of setting calculation of deviation resistance relay and explicates that under certain conditions, great errors will be made when the setting calculation of deviation resistance relay is replaced by the setting calculation of direction resistance relay. The conculsion is that generally, the two setting calculations are not replaceable.
作者 李俊梅
出处 《电力学报》 2006年第2期199-200,204,共3页 Journal of Electric Power
关键词 继电保护 微机保护 偏移阻抗继电器 relay protection microprocessor pretection deviation resistance relay
  • 相关文献

参考文献2

二级参考文献2

  • 1水力电力部.PLH-11型继电保护屏检验[M].北京:水利电力出版社,1998..
  • 2贺家李.电力系统继电保护原理[M].北京:水利电力出版社,1995..

共引文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...