摘要
600MW火电机组的厂用电与一般机组有较大差异,在厂用电切换过程中可能存在较大相角差。为保证机组厂用电合理可靠和设备安全,从理论上分析了影响相角差的主要因素有电网结构、系统运行方式和电压水平;以阳逻电厂三期工程为例,通过仿真计算验证了理论分析的结论,并定量给出了在各种电网结构和运行方式下的相角差。对今后600MW火电机组厂用电设计、运行有一定借鉴作用。
For 600MW thermal power unit, there is generally a larger angle difference than other thermal unit during unit auxiliary supply switching. To ensure a reliable switching and the equipment safety, such factors as grid structure, operation mode and system voltage level are discussed in this paper. As a example simulation on No.3 Yangluo thermal power plant is also presented.The analysis ard simulation can be used for reference on design and operation of 600MW thermal power unit auxiliary supply.
出处
《华中电力》
2006年第4期12-15,共4页
Central China Electric Power
关键词
厂用电
相角差
仿真
unit auxiliary supply
angle difference
simulation