摘要 对WMZ-41微机母差保护一次误动作过程详细描述,分析误动作原因,指出母线连接支路CT性能差异,切除外部故障后母差保护装置中会产生差流。对进一步完善设备功能和设备运行有一定借鉴作用。 This paper details the maloperation process of WMZ - 41 computer-based bus differential protection in a power accident. It analyzes the course of the accident and distinguishes different performances when bus connects branch CT. It indicates that bus differential protection would produce differential current after external failure is cut off. To pursue further perfect device function and more reliable device operation, this paper would supply some reference value.
作者 陈银胜 甘杏
出处 《继电器》 CSCD 北大核心 2006年第17期73-74,77,共3页 Relay
关键词 微机母差 误动 差流 电流互感器 computer-based bus differential motion maloperation differential current current mutual inductor