期刊文献+

程序错误造成的监控机死机两案例分析

Two cases of computer halt caused by program bugs
下载PDF
导出
摘要 以SL300和DISA100型系统为例,根据实际工作中遇到的故障,就非法和错误报文而引起的处理程序运行出错造成死机现象作了深入分析。SL300前置机死机的直接原因是接收了数据库没有配置的参数,进一步找到了内存管理问题,提出了增加寻址出错处理机制的修补措施。DISA100监控后台机死机的直接原因是接收了协议未规定的非法报文,诱因是保护管理机内存管理出错,反映了规约处理程序容错性不够的问题。 Taking SL 300 and DISA 100 systems as examples,according to real faults occurred in operation,the computer halt phenomena caused by illegal and wrong messages are analyzed. The halting of SL 300 front-end computer is found due to receiving parameters not configured in database,causing memory management problem. Addressing mistake processing r^echanism is added for it. The halting of DISA 100 supervisory computer is found due to receiving an illegal message undefined in protocols,causing memory management problem of protection manager. Poor errortolerance of protocol processing program is shown.
作者 李智勇
出处 《电力自动化设备》 EI CSCD 北大核心 2006年第10期114-116,共3页 Electric Power Automation Equipment
关键词 死机 接口 内存 数据空间 监控 过滤器 halt interface memory data space monitoring filters
  • 相关文献

参考文献8

  • 1吴维宁,张文亮.提高电力监控系统软件可靠性措施的研究[J].电力自动化设备,2003,23(3):53-54. 被引量:5
  • 2王忠明.微机计算机原理[M].西安:西安电子科技大学出版社,2003..
  • 3孙涵芳.Intel 16位单片机[M].北京航空航天大学出版社,1998..
  • 4NELSON M.串行通信开发指南[M].潇湘工作室,译.北京:中国水利水电出版社,2000.
  • 5刘红玲.微机接口实用技术[M].北京:电子工业出版社,2003..
  • 6《DISA通信规约(v2.01)》4.12.④.
  • 7《ISA300扩展CDT通信规约(Ver102)》2.4.
  • 8《ISA300基于串口保护通信规约(Ver302)》.