对中电国华北京热电分公司水汽系统氢电导率持续超标现象进行分析,认为其主要为水源水受有机物污染所致。分析了此类污染引起水汽品质变化的主要特征,为判断水源水是否受到有机物污染提供了简单实用的方法。
Directing against the phenomenon of hydroden canductivity sustaining to exceed the standard limit in steamwater system of China Power Guoha Beijing Thermal Power Branch Co, the causes have been analysed. It is believed that the main cause was due to the headwater being pollutted by organics. The main features of water and steam quality variations resulted from pollution of this kind have been pointed out and analysed. On this basis, whether the headwater to be pollutted by organics can be judged.