期刊文献+

水泵接合器的工程设计与设置 被引量:1

The Project Design and Set of the Fire Department Connection
下载PDF
导出
摘要 水泵接合器是连接室内消防管网与室外消火栓或消防车的连通器,无论是消火栓系统还是自动喷水灭火系统,水泵接合器与室外消火栓的数量关系是一一对应的关系。为了满足水泵接合器距室外消火栓或消防水池15m~40m的距离要求,建议在建筑物外设置消防专用环管,在其上四周均匀布置室外消火栓。同时分析了水泵结合器在高层建筑分区系统中的设置数量与分区关系及其水泵结合器在自喷消防系统中的合理连接方式。 Inside fire pipes and indoor fire hydrant or firefly are connected by fire department connection that is a sort of connection equipment, whether the fire hydrant systems or the sprinkler systems, the relationship between fire department connection and outside fire hydrant is described 1:1 quantity relation, outside fire hydrant must be increased in order to meet with 15 -40 meter distance that the fire department connection from the outside fire hydrant, suggesting setting up a special circle fire pip e in the outside for setting the outside fire hydrant. Analyzing the relation of the set quantity and division of the fire department connection in the tall building division and the reasonable joint ways of the fire department connection in the sprinkler systems.
出处 《工程建设与设计》 2006年第12期64-67,共4页 Construction & Design for Engineering
关键词 消防系统 工程设计 水泵接合器 fire system ,engineering design, fire department connection
  • 相关文献

参考文献5

  • 1GBJ 16-87,建筑设计防火规范[S].中华人民共和国公安部.2001.
  • 2GB50045-95.高层民用建筑设计防火规范[S].[S].中华人民共和国公安部,..
  • 3JGJ57-2000.剧场建筑设计规范[S].2000.
  • 4GBJ50084-2001.自动喷水灭火系统设计规范[S].[S].中华人民共和国公安部,..
  • 5陈秉安.浅谈水泵接合器在设计安装中存在的几个问题[J].消防技术与产品信息,1996,9(6):11-11. 被引量:1

共引文献430

同被引文献9

引证文献1

二级引证文献4

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部