摘要 根据由大元件构成的箱式并联电容器的基本参数和结构特点,推导了电压差动保护和故障后完好元件上过电压倍数的计算式,并举例作了计算和说明,讨论了初始不平衡电压的影响因素。 In terms of the basic parameters and configuration characteristics of tank type shunt capacitors which are composed of a number of larger elements, this paper educes the calculating formulas for their differential voltage protection and over-voltage times on intact elements after any element is in failure, as well as gives an example for protection calculating and explaining, then discusses some factors that affect initial imbalance voltage.
作者 杨一民
出处 《电力电容器》 2007年第1期20-25,共6页 Power Capacitors
关键词 箱式 并联电容器 放电线圈 不平衡保护 电压差动 Tank Shunt capacitor Discharge coil Imbalance voltage protection Differential voltage
  • 相关文献

参考文献5

  • 1杨昌兴,王敏.电容器装置不平衡保护灵敏度系数的取值.2002年《电力电容器学术论文集》[C].西安:电力电容器研究所,2002.
  • 2盛国钊 倪学锋.高压并联电容器组不平衡保护计算中遇到的新问题[J].无功补偿装置(武汉:武汉高压研究所),2003,.
  • 3梁琮.并联电容器组不平衡保护初始值的估算[J].电力电容器,2002(3):1-4. 被引量:18
  • 4DL/T584-1995《3-110kV电网继电保护装置运行整定规程》
  • 5日新电机(无锡)有限公司.《箱式高压并联电容装置使用说明书》