摘要
本文分析了网络机房供配电系统特点,及ATSE在网络机房中应用要求,得出四个重要结论,即网络机房应采用一体化结构的PC级ATSE;重要的网络机房,建议选用旁路隔离型、旁路抽出型或瞬间并联型ATSE;末端电源切换,建议采用静态转换开关;合理地选择ATSE的切换时间及其位数。
The paper analyzes the characteristics of power supply and distribution system in IT rooms, and the requirements for ATSE applied in IT rooms. Four conclusions are given that an integrated structure Class PC ATSE should be used in IT rooms; bypass isolated, bypass extracted and transient parallel ATSE are recommended to use in the important IT rooms; the static transfer switches are recommended to be used when switched at the power supply end; reasonably selecting the switching time and the number of position of ATSE.
出处
《智能建筑电气技术》
2007年第1期34-37,共4页
Electrical Technology of Intelligent Buildings