期刊文献+

广州蓄能水电厂B厂低频保护设计及应用 被引量:1

Design and application of under-frequency protection for Guangzhou Pumped Storage Power Station B
下载PDF
导出
摘要 广州蓄能水电厂B厂原有的低频保护系统由12个频率计组成,回路复杂,经常误动。为了解决这些弊端,采用三台GE公司的DFF1002型号的频率继电器组成新的系统,改造后系统运行稳定,动作准确度高,保障了电网的安全稳定运行。重点介绍了新系统的设计、动作原理及动作逻辑,最后对新旧系统的功能进行了比较。 After the modification, the under-frequency protection system for Guangzhou Pumped Storage Power Station PhaseⅡis composed of three DFF1002 frequency relays made by GE. Now the system is in steady operation and with high degree of accuracy. The thesis introduces the necessity for updating the old system and emphatically states the design, the function principle and the operation logic of the new system. At last compares the difference between the new system and the old one.
机构地区 广州蓄能水电厂
出处 《水电站机电技术》 2007年第1期25-26,29,共3页 Mechanical & Electrical Technique of Hydropower Station
关键词 低频保护 频率继电器 设计 原理 逻辑 under-frequency protection frequency relay: design principle logic
  • 相关文献

同被引文献7

  • 1DL/T684-1999大型发电机变压器继电保护整定计算导则[S].北京:中国电力出版社,1999.
  • 2DL/T5177--2003水力发电厂继电保护设计导则[S].北京:中国电力出版社,2003.
  • 3DL497—1992电力系统自动低频减负荷工作管理规程[S].北京:中国电力出版社,1992.
  • 4DL428--2005电力系统自动低频减负荷技术规定[S].北京:中国电力出版社,2005.
  • 5华中电力调度规程[S].武汉:华中电力调度通信中心,2011.
  • 6王维俭.电气主设备继电保护原理与应用[M].北京:中国电力出版社,2000..
  • 7赵强,刘肇旭,张丽.对中国低频减载方案制定中若干问题的探讨[J].电力系统自动化,2010,34(11):48-53. 被引量:39