ABB HPL550B2型断路器合闸故障的分析研究 被引量:3

The Analysis of a Closing Fault of the ABB HPL550B2 Circuit Breaker
下载PDF
导出
摘要 详细讲述了聊城500kV变电站一起ABBHPL550B2型断路器无法合闸故障的经过并分析了故障原因。由于合闸缓冲器漏油引起的主轴弯曲,机械联锁杆无法抬起导致断路器无法合闸。就故障原因提出了在检修维护即日常巡视中应采取的措施即注意事项。 The malfunction process of an ABB HPL550B2 circuit breaker failing to close in Liaocheng 500KV substation is illustrated and the reason is analyzed in this paper. Due to the oil leakage of the close buffer caused by bend of the main axis, the machine interlock pole failed to lift. Therefore, the circuit breaker couldn't be closed. Based on this reason, related steps and notations during the maintenance and routine examination are put forward in the article.
出处 《山东电力技术》 2007年第1期59-61,共3页 Shandong Electric Power
关键词 ABB HPL55082型断路器 合闸缓冲器 机械联锁 ABB HPL550B2 circuit breaker closing buffer machine interlock
  • 相关文献

参考文献3

  • 1.ABB HPL245-550B2型断路器产品使用手册.,..
  • 2Boeck W. , Witzmann R. Main influences on the tran sient development in gas - insulated substations(GIS. Proc. 5 th ISH, 1987 (Brauschweig, Germany).
  • 3电力工业标准汇编[S].电气卷 1997.