期刊文献+

显热除霜方式的理论分析与试验研究 被引量:13

THEORETICAL ANALYSIS AND EXPERIMENTAL STUDY ON THE SENSIBLE HEAT DEFROST
下载PDF
导出
摘要 针对四通阀换向除霜方式的不足,提出了一种新型的除霜方式-显热除霜。深入分析了显热除霜的机理和作用过程,并进行了试验研究,试验表明采用显热除霜不仅具有良好的除霜效果,还可以较大程度缩短除霜时间,同时避免四通阀换向除霜给制冷系统带来的冲击,消除“奔油”现象。除霜过程中系统供热水温度波动在5℃以内。 A new defrosting method-sensible heat defrost was promoted to overcome some disadvantages of conventional four-way valve reversion defrost. Its principle and working process were analyzed, and experiments were carried out. Experimental results showed that sensible heat defrost not only had a favorable defrosting performance, but also shortened the defrosting time. Furthermore, it can void fluctuating working condition and solve the problem of large amount of oil rush out from compressor, which can be caused by using four-way valve reversion defrost. Also, in the defrosting process, the hot water temperature fluctuates was within 5℃.
出处 《工程热物理学报》 EI CAS CSCD 北大核心 2006年第4期559-561,共3页 Journal of Engineering Thermophysics
基金 国家自然科学基金资助项目(No.50376052)
关键词 显热除霜 试验研究 风冷热泵 换向除霜 sensible heat defrost experimental study air source heat pump reverse cycle defrost
  • 相关文献

参考文献4

  • 1J Watters Richard,D L O'Neal,Yang Jianxin.Effect of Fin Staging on Frost/Defrost Performance of A TwoRow Heat Pump Evaporator at Standard Test Conditions.2001,107(2):240-249
  • 2Clint Finstad,V C Mei,F C Chen,et al.Warm LiquidDefrosting for Supermarket Refrigerated Display Cases.ASHRAE Transactions,2002,108(1):669-672
  • 3Kenneth Elovitz,John Behr,P S Hrnjak,et al.Defrost Issues in Indirectly Refrigerated Display Cases.ASHRAE Transactions,2001,107(2):466-472
  • 4梁彩华,张小松,巢龙兆,刘一民.显热除霜方式与逆向除霜方式的对比试验研究[J].制冷学报,2005,26(4):20-24. 被引量:31

二级参考文献12

  • 1韩慧秋,董威.空气源热泵机组除霜问题分析[J].长春工程学院学报(自然科学版),2003,4(1):14-16. 被引量:2
  • 2姚杨,马最良.空气源热泵冷热水机组室外换热器结霜工况下数学模型的建立[J].流体机械,2001,29(10):50-52. 被引量:12
  • 3Yoshinobu Yamazaki. Inverter Air-Conditioners with Thermal Storage Unit and Fuzzy Logic Control System.REFRIGERATION, 1992,67(772):14-22.
  • 4Masami Hayashi,Shigeru Nariai,Masaya Hayama.Develoment of Scroll Inverter Air Conditioners,REFRIGERTION, 1992,67(772):,51-57.
  • 5Watters Richard J O'Neal, Dennis L Yang, Jianxin. Effect of fin staging on frost/defrost performance of a two-row heat pump evaporator at standard test conditions. 2001,107(2):240-249.
  • 6Finstad, Clint Mei V C Chen, F C et al. Warm liquid defrosting for supermarket refrigerated display cases. ASHRAE Transactions, 2002,108 (1):669-672.
  • 7Elovitz, Kenneth Behr, John Hrnjak P S et al . Defrost issues in indirectly refrigerated display cases. ASHRAE Transactions,2001,107 (2):466-472.
  • 8Mago, Pedro J Al-Mutawa, Nawaf K Theen et al. Psychrometrics in the supersaturated frost zone. ASHRAE Transactions, 2001.107 (2):753-767.
  • 9陈汝东,许东晟.制冷装置除霜方法的研究[J].同济大学学报(自然科学版),1998,26(5):566-569. 被引量:14
  • 10石文星,李先庭,邵双全.房间空调器热气旁通法除霜分析及实验研究[J].制冷学报,2000,21(2):29-35. 被引量:80