期刊文献+

极化冷冻机油添加剂的节能性分析 被引量:1

Energy Efficiency Analysis of Polarized Refrigerant Oil Additive
下载PDF
导出
摘要 本文分析了极化冷冻机油添加剂(PROA)的节能机理,讨论了目前对极化冷冻机油添加剂研究中存在的一些争议。并结合工程实例对实际运行的冷水机组进行了现场测试,对添加前后系统的性能和能耗进行了比较分析。结果表明,极化冷冻机油添加剂节能效果并不显著。 The energy efficiency mechanism of Polarized Refrigerant Oil Additive (PROA) is analyzed. Some disputes in study about PROA recently are discussed. The performance and energy consumption of the system before and after treatment are compared by a field test. The result shows that it cannot save significant energy for the system with PROA
出处 《建筑热能通风空调》 2007年第2期37-39,共3页 Building Energy & Environment
关键词 极化冷冻机油添加剂 节能 冷水机组 现场测试 polarized refrigerant oil additive (PROA), energy efficiency, chiller, field test
  • 相关文献

参考文献6

共引文献1

同被引文献5

  • 1马素贞,龙惟定,马宏权.欧盟建筑能效指令及其在欧洲的实施[J].暖通空调,2006,36(8):86-90. 被引量:8
  • 2Efficiency Valuation Organization. International performance measurement and verification protocol- concepts and practices for determining energy and water savings[EB/OL], http: ///www. evo-world. org,2007.
  • 3International performance measurement and verification protocol-volume Ⅰ(2002), concepts and practices for determining energy and water savings prepared by Efficiency Valuation Organization [EB/ OL]. http:// www. evo-world. org.
  • 4上海市政协人口资源环境建设委员会.上海市住宅建筑节能现状调研,2006.
  • 5中国金茂(集团)股份有限公司工程部,同济大学.金茂大厦能耗模拟与分析总报告.