期刊文献+

一种灵活的防振荡结线

An Agile Anti-Oscillation Electrical Connection
下载PDF
导出
摘要 长葛市佛耳岗水库水电站电抗分流式发电机并列运行时,出现剧烈无功振荡。采用副绕组顺转120°接电抗器,改变抽头位置,增设双投开关,解决了振荡问题,给电站提供了多种运行方式。 In the Fuergang hydropower station, there happened a violent reactive power oscillation when the small reactor-starting generator was put into operating with the large generator. For overcoming this trouble, the reactor's windings were reconnected after the subwinding phase shifted 120°clockwise and the tap of mainwinding shifted near the neutral point.In addition,a two-way switch was installed in the excitation circuit. Thence, the oscillation disappeared, and the generators can be operated on various mode.
作者 蒋明鑫
出处 《中国农村水利水电》 1997年第3期7-8,共2页 China Rural Water and Hydropower
关键词 无功振荡 顺转法 双投开关 水电站 发电机运行 reactive power oscillation clockwise shift two-way switch