通过使用不对称分量法和故障过程中负序网络图,计算发变组主开关在一相拒合和一相拒分两种不同非全相过程中的负序电流量,比较发电机所能承受负序能力情况,分析发变组启动失灵保护负序电流判据整定计算与保护的灵敏度之间的关系,提出发变组启动失灵保护负序电流判据整定计算依据的建议,并提出了在发电机非全相时运行单位的处理措施和注意事项。
By the conventional unsymmetrical method and its negative-sequence network of fault calculation,this paper calculates negative-sequence current in open phase with one phase open or one phase closed of generator transformer broken.It analyses relations between settings calculation of negative-sequence current for startup failure protection and its sensitivity. It also proposes some suggestions on setting calculation of negative-sequence current for startup failure protection,and attentions on open phase of generator transformer unit.
出处
《继电器》
CSCD
北大核心
2007年第7期83-85,共3页
Relay
关键词
发变组
启动失灵
负序判据
非全相
整定计算
序网络
generator transformer unit
startup failure protection
negative-sequence current constant value
open-phase
setting calculation
sequence network