期刊文献+

RCS-9653型备用电源自投装置的应用研究 被引量:1

Application of RCS-9653 type automatic throw-in equipment of emergency power supply
下载PDF
导出
摘要 RCS-9653型备用电源自投装置可实现220 kV电压等级以下,不同电气主接线方式的变电站和发电厂内多种备用电源自投情况,但是,对于变电站电气主接线为双母线接线的变电站,当运行方式发生变化时,目前的RCS-9653型备用电源自投装置还存在一些问题,不能灵活地满足运行方式变化的要求。通过对RCS-9653型备用电源自投装置分析研究,从工程实际情况出发,在尽量不改变装置软件及硬件的情况下,制定了RCS-9653型备用电源自投装置在220 kV变电站电气主接线为双母线情况下的接线方法,并对运行方式的限制,使其适应双母线及单母线的运行方式的实际需要。 RCS-9653 type automatic throw-in equipment of emergency power supply can be applied in substation bus arrangement under 220kV voltage class, however, in substations applied two-wire system, when mode of operation changed, there were still some problems that can't meet the requirement. In this paper, by analyzing RCS-9653 type automatic throw-in equipment of emergency power supply, mode of connection, whose bus arrangement was two-wire system, is given. The restriction of mode of operation can meet the requirement of not only two-wire system but also single-wire system.
出处 《继电器》 CSCD 北大核心 2007年第8期80-82,共3页 Relay
关键词 备用电源自投 主接线 变电站 发电厂 automatic throw-in equipment of emergency power supply bus arrangement substation power plant
  • 相关文献

参考文献1

  • 1南京南瑞继保电气有限公司.RCS-9653备用电源自投装置使用说明书[Z].

同被引文献3

引证文献1

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部